Fan Coil Thermostat Controller
Specification and Installation Instructions
TFHB24F3XYZ2-EBA-140113.docx
Model
TFHB24F3XYZ2
with Humidity Sensor and BACnet Communication
Description
The TFHB24F3XYZ2 is a fully configurable controller designed
specifically for 2 pipe and 4 pipe fan coil applications. No
additional modules are required as the required inputs, outputs
and control algorithms are built into the unit. The
TFHB24F3XYZ2 also provides support for networked
communications via the BACnet MS/TP protocol. The
TFHB24F3XYZ2 also provides an internal humidity sensor to
dehumidify the controlled space when the humidity is too high
by cooling with the fan on low to create condensate.
TFHB24F3XYZ2
Applications
Heating, cooling and reheat
2 pipes or 4 pipes
Auxiliary heating sources, such as electric baseboards, can
also be applied
Features
Backlit LCD with simple icon and text driven menus
Configurable inputs and outputs
2 Pipes with Analog, ON/OFF, or Floating option
4 Pipes with Analog, ON/OFF, or Pulse option
Internal humidity sensor and dehumidification sequence
(compensated by auto activation of reheat output)
Precise temperature control with programmable PI function
Selectable Fahrenheit or Celsius scale
Independent cool and heat setpoint for No Occupancy
Lockable setpoint, control mode, and fan mode
Selectable internal or external temperature sensor
Changeover by contact or external temperature sensor
Selectable proportional control band and dead band
Anti-freeze protection
BACnet® MS/TP @ 9600, 19200, 38400, or 76800 bps
o Selectable MAC address
o Automatic or manual device instance assignment
o Automatic baud rate detection
o Copy and broadcast configuration to other
networked TFHB24F3XYZ2 modules
Typical Application
Fan coil applications provide heating and cooling to a zone by
circulating hot and cold air depending on the demand to maintain
an optimum temperature in the selected space. A fan coil setup
typically consists of fan coil units, source for hot and cold water,
and a pipe system for distribution. When there is a demand for
heating, the hot water is supplied to the unit through the source
and passes over the heating coil, and the hot air is pushed into
the zone by the fan. When there is a demand for cooling, the cold
water is supplied to the unit through the source and passes over
the cooling coil, and the cold air is pushed into the zone by the
fan.
* Consult www.neptronic.com for details on these Neptronic products.
Technical Specifications
Description
Fan Coil Thermostat Controller
Inputs
1 Digital input (24Vac or dry contact)
1 Analog input (external temperature sensor 10Kohms)
1 Analog input (change over 10Kohms or dry contact)
Outputs 1 Fan analog or 3 Fan speed dry contracts 24Vac, 1A max 3A in-rush)
2 Analog outputs (cooling and/or heating 0-10Vdc
1 Analog output (local reheat 0-10Vdc)
2 TRIAC outputs (cooling and/or heating) 24Vac, 0.3A max fused / TRIAC
1 TRIAC output (local reheat) 24Vac, 0.3 max fused TRIAC
Power supply
22 to 26Vac 50/60Hz
Power consumption
1VA max
Setpoint range
10ºC to 40ºC [50ºF to 104ºF], Humidity 10 to 65% RH
External sensor range
0ºC to 50ºC [32ºF to 122ºF]
Control accuracy
Temperature: ±0.4ºC [0.8ºF], Humidity: ±3.5%
Proportional band
0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/reheat independent)
Dead Band
0ºC to 5ºC [0ºF to 10ºF] adjustable (heat/cool/reheat independent)
Electrical connection
0.8 mm
2
[18 AWG] minimum
Vista de pagina 0
1 2 3 4 5 6 ... 15 16

Indice de contenidos

Pagina 1 - TFHB24F3XYZ2

Fan Coil Thermostat Controller Specification and Installation Instructions TFHB24F3XYZ2-EBA-140113.docx Model TFHB24F3XYZ2 with Humidity Sensor and

Pagina 2 - ºF / º C

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 10 Humidity Settings 44. “inside humidity se

Pagina 3

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 11 52. “Select begin address” Default: Ran

Pagina 4 - Programming Mode

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 12 BACnet Setup Operation Mode The BACnet Set

Pagina 5

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 13 Operation Mode The Mode Selector Jumper (

Pagina 6

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 14 Control Mode To access the Control Mode, p

Pagina 7

Notes Recycling at end of life: please return this product to your Neptronic local distributor for recy

Pagina 8

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com Toll free in North A

Pagina 9

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 2 Description Fan Coil Thermostat Controller

Pagina 10

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 3 Wiring - 4 Pipe Terminal Description Detail

Pagina 11 - 56. “0153000”

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 4 Programming Mode The Mode Selector Jumper

Pagina 12 - BACnet Setup Operation Mode

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 5 6. “adjust temper control mode” Default:

Pagina 13 - Operation Mode

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 6 13. “Ch over temper sensor” Default: Ran

Pagina 14 - Fan Speed Selection Mode

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 7 20. “max vdc analog output cooling ” De

Pagina 15

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 8 27. “control ramp cooling” Default: Rang

Pagina 16

Fan Coil Thermostat Controller Specification and Installation Instructions www.neptronic.com Page | 9 36. “enable fan auto mode” Default: Rang

Comentarios a estos manuales

Sin comentarios